Single Hole Electrical Flex Lugs - 1/0 to 4/0 AWG

Features / Benefits

  • Super-Heavy Duty Wall Thickness: Pullout Resistance/Corrosion Resistance
  • Extended Barrel: Double Crimp: Added Pullout Resistance
  • Chamfered Barrel Entry: Ease of Wire Insertion
  • Annealed Copper Barrel: Strong Pullout Resistance
  • Work-hardened Tang: Tear Resistant
  • Square Tang: Terminal Block & Secure Fit
  • Square Transition: Full Cable Insertion
  • Complete Range of Studholes
  • Tin Plating: Corrosion Resistance
  • UL/CUL Listed: Assures Safety and Effectiveness
  • Color-Code with your Logo!
  • Barrel Configuration: Standard / Long
  • Barrel Style: Chamfer
  • Finish: Tinned
  • Number of Crimps: 1

Single Hole Electrical Lugs 8 to 1 Gauge Drawing

View a larger table
Char. ID “A” O.D. “B” I.D. “C” BL “D” OL “E” TW “E” TT “F” “G” Color Code T&B Die Burndy Die
Tolerance
Part No. AWG Ga. Nom. Stud Size +/- .010 +/- .010 +/- .010 +/- .030 +/- .060 +/- .030 +/- .010 +/- .030
EL10F14 1/0Flex 1/4 0.265 0.56 0.46 0.94 2.55 0.88 0.1 0.42 PNK 15526 U26RT
EL10F516 1/0Flex 5/16 0.35 0.56 0.46 0.94 2.55 0.88 0.1 0.62 PNK 15526 U26RT
EL10F38 1/0Flex 3/8 0.4 0.56 0.46 0.94 2.55 0.88 0.1 0.42 PNK 15526 U26RT
EL10F12 1/0Flex 1/2 0.525 0.56 0.46 0.94 2.55 0.88 0.1 0.62 PNK 15526 U26RT
EL10F58 1/0Flex 5/8 0.6 0.56 0.46 0.94 2.55 1 0.1 0.69 PNK 15526 U26RT
EL20F14 2/0Flex 1/4 0.265 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLK 15509 U27RT
EL20F516 2/0Flex 5/16 0.35 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLK 15509 U27RT
EL20F38 2/0Flex 3/8 0.4 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLK 15509 U27RT
EL20F12 2/0Flex 1/2 0.525 0.62 0.51 0.94 2.75 0.94 0.11 0.69 BLK 15509 U27RT
EL20F58 2/0Flex 5/8 0.6 0.62 0.51 0.94 2.75 1.05 0.11 0.69 BLK 15509 U27RT
EL30F14 3/0Flex 1/4 0.265 0.68 0.56 1 2.6 1.02 0.1 0.38 ORNG 15510 U28RT
EL30F516 3/0Flex 5/16 0.35 0.68 0.56 1 2.6 1.02 0.1 0.38 ORNG 15510 U28RT
EL30F38 3/0Flex 3/8 0.4 0.68 0.56 1 2.6 1.02 0.1 0.38 ORNG 15510 U28RT
EL30F12 3/0Flex 1/2 0.525 0.68 0.56 1 2.8 1.02 0.1 0.38 ORNG 15510 U28RT
EL30F58 3/0Flex 5/8 0.6 0.68 0.56 1 2.8 1.02 0.1 0.38 ORNG 15510 U28RT
EL40F14 4/0Flex 1/4 0.265 0.76 0.625 1 2.6 1.1 0.11 0.38 PRPL 15510 U28RT
EL40F516 4/0Flex 5/16 0.35 0.76 0.625 1 2.6 1.1 0.11 0.38 PRPL 15510 U28RT
EL40F38 4/0Flex 3/8 0.4 0.76 0.625 1 2.6 1.1 0.11 0.38 PRPL 15510 U28RT
EL40F12 4/0Flex 1/2 0.525 0.76 0.625 1 2.8 1.1 0.11 0.38 PRPL 15510 U28RT
EL40F58 4/0Flex 3/8 0.6 0.76 0.625 1 2.8 1.1 0.11 0.38 PRPL 15510 U28RT
Single Hole Electrical Lugs 8 to 1 Gauge Drawing
Char. Studhole “A” O.D. “B” I.D. “C” Bbl. Length “D” O.A.L. “E” Tang Width “E” Tang Thickness “F” Stud Clearance “G” Color Code T&B Die Burndy Die
Tolerance
Part No. AWG Ga. Nom. Stud Size +/- .010 +/- .010 +/- .010 +/- .030 +/- .060 +/- .030 +/- .010 +/- .030
EL10F14 1/0Flex 1/4 0.265 0.56 0.46 0.94 2.55 0.88 0.1 0.42 PINK 15526 U26RT
EL10F516 1/0Flex 5/16 0.35 0.56 0.46 0.94 2.55 0.88 0.1 0.62 PINK 15526 U26RT
EL10F38 1/0Flex 3/8 0.4 0.56 0.46 0.94 2.55 0.88 0.1 0.42 PINK 15526 U26RT
EL10F12 1/0Flex 1/2 0.525 0.56 0.46 0.94 2.55 0.88 0.1 0.62 PINK 15526 U26RT
EL10F58 1/0Flex 5/8 0.6 0.56 0.46 0.94 2.55 1 0.1 0.69 PINK 15526 U26RT
EL20F14 2/0Flex 1/4 0.265 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLACK 15509 U27RT
EL20F516 2/0Flex 5/16 0.35 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLACK 15509 U27RT
EL20F38 2/0Flex 3/8 0.4 0.62 0.51 0.94 2.6 0.94 0.11 0.69 BLACK 15509 U27RT
EL20F12 2/0Flex 1/2 0.525 0.62 0.51 0.94 2.75 0.94 0.11 0.69 BLACK 15509 U27RT
EL20F58 2/0Flex 5/8 0.6 0.62 0.51 0.94 2.75 1.05 0.11 0.69 BLACK 15509 U27RT
EL30F14 3/0Flex 1/4 0.265 0.68 0.56 1 2.6 1.02 0.1 0.38 ORANGE 15510 U28RT
EL30F516 3/0Flex 5/16 0.35 0.68 0.56 1 2.6 1.02 0.1 0.38 ORANGE 15510 U28RT
EL30F38 3/0Flex 3/8 0.4 0.68 0.56 1 2.6 1.02 0.1 0.38 ORANGE 15510 U28RT
EL30F12 3/0Flex 1/2 0.525 0.68 0.56 1 2.8 1.02 0.1 0.38 ORANGE 15510 U28RT
EL30F58 3/0Flex 5/8 0.6 0.68 0.56 1 2.8 1.02 0.1 0.38 ORANGE 15510 U28RT
EL40F14 4/0Flex 1/4 0.265 0.76 0.625 1 2.6 1.1 0.11 0.38 PURPLE 15510 U28RT
EL40F516 4/0Flex 5/16 0.35 0.76 0.625 1 2.6 1.1 0.11 0.38 PURPLE 15510 U28RT
EL40F38 4/0Flex 3/8 0.4 0.76 0.625 1 2.6 1.1 0.11 0.38 PURPLE 15510 U28RT
EL40F12 4/0Flex 1/2 0.525 0.76 0.625 1 2.8 1.1 0.11 0.38 PURPLE 15510 U28RT
EL40F58 4/0Flex 3/8 0.6 0.76 0.625 1 2.8 1.1 0.11 0.38 PURPLE 15510 U28RT

Product Options

  • All parts have sight hole/inspection port as standard feature. For no sight hole, add “XSH” at end of part number.
  • All parts listed here are straight tangs. 45 and 90 Degree bends are available. Add “45” or “90” at end of part number (after “XSH”)
  • All parts listed here are standard tang width (normal tube flattening geometry). For Narrow Tang (“NT”) contact us.
  • Extended barrels, short barrels, extended tangs, special studhole patterns, hundreds of options, JUST ASK!

Description:   ASK Power’s Compression, Single Connector, and Standard Barrel Lugs incorporate squared tangs, chamfered entry, and steep-sloping transitions. Available in crimp or solder lugs. Tinned Military Specification plating. Lugs formed from high-purity annealed copper with heavy duty walls. Provides excellent ductility,conductivity, security and tang strength. Lugs accommodate wire sizes 8 Gauge through 4/0 AWG and from 250 to1000 MCM. Crimp barrels are sized to closely match commercial battery and power cable strand diameters. Non-insulated lugs for crimped or soldered wire connection and bolted termination. Wire gauge and UL mark appear clearly on wire barrel.

Recommended Uses:  These cable lugs are used for power transmission and/or grounding in telcom, electrical, and transformer applications. Square tang compression lugs fix
cable connections firmly in terminal blocks or on grounding busbar slots for efficient cable organization. Chamfered barrels ease insertion of highly stranded battery cable into funnel-entry crimp barrels.

Tooling and Application: Crimp lugs can be applied to cable via hand-actuated or hydraulic crimp tools. Our Heavy Duty Copper Lugs are UL Listed (UL 486 A), using the Thomas and Betts M5 or the Burndy tool; these lugs can also be connected by solder-dipping. Single crimp lugs provide strong pullout resistance. Color-coding provides field installation guidance by matching cable, lug, and crimper color codes per industry-accepted standards.

  • Tel: 866-457-4830